Brand Name : GDZX

Model Number : ZX-PDF

Certification : ISO9001

Place of Origin : China

MOQ : 1Set

Payment Terms : L/C, T/T, Western Union, MoneyGram,

Supply Ability : 1200Sets/ year

Delivery Time : 3-20 work day

Packaging Details : Carton or Wooden Case

Working power supply : AC220V±15%

Environment temperature : -20℃—45℃

Relative humidity : 0—90%

DC source output range : 0-260V

Voltage output regulation fineness : 0.2%

Maximum output current : 1.2A

Contact Now

Earth Insulation Tester

AC220V DC System Ground / Earth Fault Detector Testing Equipment

Features

1. On line or off line testing the grounding supervising device or ground fault locator

2. Positive grounding test function

3. Negative grounding test function

4. Two-pole grounding test function

5. Voltage accuracy test function

6. Voltage limit exceeding alarm test function

7. AC grounding test function

8. Balance bridge test function

9. System counter distributed capacitance test function

10. Branch counter distributed capacitance test function

11. Signal analysis function

12. Loop simulation function, can do device ability test under loop current

Technical Indicators

1. Working environment:

a) Working power supply: AC220V±15%

b) Environment temperature:-20℃—45℃

c) Relative humidity: 0—90%

2. Controllable DC source parameters:

a) DC source output range: 0-260V

b) Voltage output regulation fineness: 0.2%

c) Maximum output current: 1.2A

3. AC power source parameters:

a) Output voltage level: AC220V, AC50V

4. DC voltage measurement

a) DC voltage measuring resolution: 0.1V

b) Positive grounding voltage accuracy: 0.1%

c) Negative grounding voltage accuracy: 0.1%

d) System voltage measuring accuracy: 0.1%

5. Positive Negative insulation resistance parameters:

a) Resistance regulation range: : 0-256 kΩ

b) Resistance regulation space: 1 kΩ

6. Branch positive negative grounding distributed capacitance parameters:

a) regulation range: 0-16uF

b) regulation space: 1uF

7. System positive negative grounding distributed capacitance parameters

a) Regulation range: 0-125uF

b) Regulation space: 1uF

8. Test Setting parameters

a) Selectable testing point group number: 1-5 groups

b) Testing interval setting range: 5-999S

c) Testing time setting range: 5-999S

9. Display and touch screen parameters:

a) Display screen: 5.6”TFT

b) Screen resolution 65536 color 640X480

c) Touch screen resolution: 4096 dots


Product Tags:

AC220V Earth Fault Detector

      

5.6" TFT Earth Fault Detector

      

AC220V Ground Fault Detector

      
Buy cheap DC AC220V Loop Simulation Earth Fault Detector With 5.6" TFT product

DC AC220V Loop Simulation Earth Fault Detector With 5.6" TFT Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Wuhan GDZX Power Equipment Co., Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)